Product

The Nova SST platform

A medium-voltage solid state transformer that converts 10–13.8 kV AC directly to 800 VDC. It uses high-frequency power conversion and a medium-frequency transformer for MV/LV isolation, all in one factory-built lineup.

10–13.8 kV AC
Input voltage
800 VDC
Output voltage
3 MW
Rated power (base model)
98.5 %
Peak efficiency
Configurations

Power in building blocks

Each lineup is built from 1.5 MW power modules. Add modules to reach 3 MW or 4.5 MW and match the architecture you're designing.

Phased deployment
1.5 MW

One SST per POD with distributed architecture. Commission and expand POD by POD, and keep any fault contained to a single POD.

High density
4.5 MW

For large new AI campuses planned across many PODs, with support for distributed-redundant and catcher redundancy schemes.

Highlights

Agile. Intelligent. Reliable. Safe.

Agile

  • 98.5% peak efficiencySingle-stage conversion cuts losses and carbon.
  • 312 kW/m² power densityAbout 29 kW/ft², with a footprint up to 50% smaller.
  • Up to 50% faster deliveryAn integrated lineup replaces multiple vendors' equipment.
  • Modular 1.5 MW blocksWorks with mainstream data center architectures.

Intelligent

  • Digital twin validationSimulate the power architecture before you deploy it. It's designed to work with NVIDIA's DSX AI-factory ecosystem.
  • Component-level fault predictionSpots failing critical components early.
  • Online insulation monitoringGives early warning of insulation faults.
  • Waveform recordingSecond-level fault recording for fast root-cause analysis.

Reliable

  • 99.999% system availability6+3 module redundancy roughly doubles MTBF.
  • MV bypass fault tolerancePartitioned MV/LV zones keep faults isolated.
  • 20% longer service lifeIntelligent module rotation spreads the wear.
  • Zero-downtime maintenanceHot-swappable LV modules, and MV module swaps in 15 minutes or less.

Safe

  • Vacuum-insulated transformerPartial discharge below 10 pC at 21 kV, and none at the cabinet level.
  • 95 kV lightning impulse42 kV AC, 1-minute power-frequency withstand.
  • Arc-free by designPhase-to-phase cabinet isolation and top-directed pressure relief.
  • Triple electrical protectionIncludes a 1.5× output current limit.
Inside the lineup

Three cabinets, one integrated system

Power flows left to right: medium voltage comes into the input cabinet, gets converted in the power cabinet, and leaves the output cabinet as regulated 800 VDC.

Input cabinet
  • MV circuit breaker for fast fault interruption
  • High-efficiency reactor for harmonic suppression and lower losses
Power cabinet 2 × 1.5 MW
  • MV power modules
  • Medium-frequency transformer (MFT) modules
  • Hot-swappable LV modules
Output cabinet
  • Intelligent main control system
  • Online insulation monitoring
  • 2N auxiliary power for uninterrupted controls
MV power module

Built for uptime

  • 6+3 redundancy doubles MTBF
  • Inherent H-bridge safety through component, circuit and system-level protection
  • Quick-plug design means a swap takes 15 minutes or less
MFT module

Vacuum-insulated isolation

  • Partial discharge below 10 pC at 21 kV
  • 42 kV AC/1 min power-frequency withstand
  • 95 kV lightning impulse
  • 99.6% transformer efficiency
LV module

Single-person service

  • Hot-swappable for zero-downtime maintenance
  • About 11 kg (24 lb) per module
  • High-reliability breaking protection with a 1.5× current limit
800 VDC ecosystem

A complete DC power system

Supporting converters connect to the same 800 VDC bus, so backup power, AC loads and load swings are all covered.

Emergency backup power

DC/DC converter for lithium-ion or lead-acid batteries, supporting a range of backup configurations.

AC load compatibility

DC/AC converter that serves CDUs, precision air conditioning and network equipment.

Load fluctuation smoothing

DC/DC converter for supercapacitors and flywheels, which ride through the sharp swings of AI training loads.

Technical specifications

3 MW base model

ParameterSpecification
Electrical
Rated power3 MW (1.5 MW per power module; 1.5 / 3 / 4.5 MW configurations)
Input voltage10–13.8 kV AC
Input voltage range−15% to +10%
Input frequency50 / 60 Hz
Maximum input current108 A (3 MW model at 10 kV input and 125% output overload)
Output voltage800 VDC
Output voltage accuracy±1%
Overload capability105% continuous · 110% for 60 min · 125% for 10 min
Peak efficiency98.5%
Mechanical & environmental
Dimensions (W × D × H)6,000 × 1,600 × 2,400 mm (≈ 236 × 63 × 94.5 in, 3 MW model)
Operating temperature0 to 40 °C (32 to 104 °F)
Storage temperature−40 to 70 °C (−40 to 158 °F)
Altitude2,000 m (6,560 ft)
Operating relative humidity≤ 90% (40 °C ± 2 °C)
Storage relative humidity≤ 95% (40 °C ± 2 °C)
CoolingForced air
Protection ratingIP20
Controls & maintenance
LV hot swapSupported
HMITouchscreen
CommunicationRS-485 / Ethernet · Modbus RTU / Modbus TCP

Imperial values are converted for reference. Specifications are subject to change. Contact us for the current datasheet and certification status.

Get the datasheet and a layout for your site

Tell us your utility voltage, IT load and redundancy scheme, and we'll match you to a configuration.

Request a datasheet →