The Nova SST platform
A medium-voltage solid state transformer that converts 10–13.8 kV AC directly to 800 VDC. It uses high-frequency power conversion and a medium-frequency transformer for MV/LV isolation, all in one factory-built lineup.
Power in building blocks
Each lineup is built from 1.5 MW power modules. Add modules to reach 3 MW or 4.5 MW and match the architecture you're designing.
One SST per POD with distributed architecture. Commission and expand POD by POD, and keep any fault contained to a single POD.
The base model, for new builds or 2N retrofits. It can also be configured to 2.5 MW to replace a conventional 2.5 MW transformer while you keep the existing LV distribution.
For large new AI campuses planned across many PODs, with support for distributed-redundant and catcher redundancy schemes.
Agile. Intelligent. Reliable. Safe.
Agile
- 98.5% peak efficiencySingle-stage conversion cuts losses and carbon.
- 312 kW/m² power densityAbout 29 kW/ft², with a footprint up to 50% smaller.
- Up to 50% faster deliveryAn integrated lineup replaces multiple vendors' equipment.
- Modular 1.5 MW blocksWorks with mainstream data center architectures.
Intelligent
- Digital twin validationSimulate the power architecture before you deploy it. It's designed to work with NVIDIA's DSX AI-factory ecosystem.
- Component-level fault predictionSpots failing critical components early.
- Online insulation monitoringGives early warning of insulation faults.
- Waveform recordingSecond-level fault recording for fast root-cause analysis.
Reliable
- 99.999% system availability6+3 module redundancy roughly doubles MTBF.
- MV bypass fault tolerancePartitioned MV/LV zones keep faults isolated.
- 20% longer service lifeIntelligent module rotation spreads the wear.
- Zero-downtime maintenanceHot-swappable LV modules, and MV module swaps in 15 minutes or less.
Safe
- Vacuum-insulated transformerPartial discharge below 10 pC at 21 kV, and none at the cabinet level.
- 95 kV lightning impulse42 kV AC, 1-minute power-frequency withstand.
- Arc-free by designPhase-to-phase cabinet isolation and top-directed pressure relief.
- Triple electrical protectionIncludes a 1.5× output current limit.
Three cabinets, one integrated system
Power flows left to right: medium voltage comes into the input cabinet, gets converted in the power cabinet, and leaves the output cabinet as regulated 800 VDC.
- MV circuit breaker for fast fault interruption
- High-efficiency reactor for harmonic suppression and lower losses
- MV power modules
- Medium-frequency transformer (MFT) modules
- Hot-swappable LV modules
- Intelligent main control system
- Online insulation monitoring
- 2N auxiliary power for uninterrupted controls
Built for uptime
- 6+3 redundancy doubles MTBF
- Inherent H-bridge safety through component, circuit and system-level protection
- Quick-plug design means a swap takes 15 minutes or less
Vacuum-insulated isolation
- Partial discharge below 10 pC at 21 kV
- 42 kV AC/1 min power-frequency withstand
- 95 kV lightning impulse
- 99.6% transformer efficiency
Single-person service
- Hot-swappable for zero-downtime maintenance
- About 11 kg (24 lb) per module
- High-reliability breaking protection with a 1.5× current limit
A complete DC power system
Supporting converters connect to the same 800 VDC bus, so backup power, AC loads and load swings are all covered.
Emergency backup power
DC/DC converter for lithium-ion or lead-acid batteries, supporting a range of backup configurations.
AC load compatibility
DC/AC converter that serves CDUs, precision air conditioning and network equipment.
Load fluctuation smoothing
DC/DC converter for supercapacitors and flywheels, which ride through the sharp swings of AI training loads.
3 MW base model
| Parameter | Specification |
|---|---|
| Electrical | |
| Rated power | 3 MW (1.5 MW per power module; 1.5 / 3 / 4.5 MW configurations) |
| Input voltage | 10–13.8 kV AC |
| Input voltage range | −15% to +10% |
| Input frequency | 50 / 60 Hz |
| Maximum input current | 108 A (3 MW model at 10 kV input and 125% output overload) |
| Output voltage | 800 VDC |
| Output voltage accuracy | ±1% |
| Overload capability | 105% continuous · 110% for 60 min · 125% for 10 min |
| Peak efficiency | 98.5% |
| Mechanical & environmental | |
| Dimensions (W × D × H) | 6,000 × 1,600 × 2,400 mm (≈ 236 × 63 × 94.5 in, 3 MW model) |
| Operating temperature | 0 to 40 °C (32 to 104 °F) |
| Storage temperature | −40 to 70 °C (−40 to 158 °F) |
| Altitude | 2,000 m (6,560 ft) |
| Operating relative humidity | ≤ 90% (40 °C ± 2 °C) |
| Storage relative humidity | ≤ 95% (40 °C ± 2 °C) |
| Cooling | Forced air |
| Protection rating | IP20 |
| Controls & maintenance | |
| LV hot swap | Supported |
| HMI | Touchscreen |
| Communication | RS-485 / Ethernet · Modbus RTU / Modbus TCP |
Imperial values are converted for reference. Specifications are subject to change. Contact us for the current datasheet and certification status.
Get the datasheet and a layout for your site
Tell us your utility voltage, IT load and redundancy scheme, and we'll match you to a configuration.